PWS-level water intelligence

The Woodlands Water Quality System Lookup

Compare 2025 water-quality measurements across 11 Woodlands-area PWSs while keeping every result tied to its district and report.

✓ Official sources✓ System-specific✓ No invented city averages
Evidence status

Coverage model: Eleven district PWSs across two counties

Use the district map, Township utility lookup, or current water bill to match the address before opening the applicable report.

Measurements published

The Woodlands is not one public water system. Ten Woodlands Water-managed MUDs cover the Montgomery County portion, while Harris-Montgomery Counties MUD No. 386 independently serves parts of Creekside Park in Harris County.

System resolution

Which water system applies?

The Woodlands MUD No. 1

TX1700471

2025: chlorine 1.91 mg/L average; HAA5 15 ppb and TTHM 41 ppb highest LRAA. Lead 1.07 ppb and copper 0.252 ppm at the 90th percentile for 2021–2023.

Montgomery County MUD No. 6

TX1700090

2025: chlorine 2.05 mg/L average; HAA5 18 ppb and TTHM 59 ppb highest LRAA. Lead 3.32 ppb and copper 0.194 ppm at the 2024 90th percentile.

Montgomery County MUD No. 7

TX1700169

2025: chlorine 1.81 mg/L average; HAA5 21 ppb and TTHM 58 ppb highest LRAA. Lead 1.7 ppb and copper 0.151 ppm at the 2023–2025 90th percentile. The CCR also reports a lead-and-copper monitoring violation: 29 compliant samples were counted because one sample was not from the approved site list; follow-up was scheduled for 2026.

The Woodlands Metro Center MUD

TX1700309

2025: chlorine 1.79 mg/L average; HAA5 9 ppb and TTHM 42 ppb highest LRAA. Lead 1.42 ppb and copper 0.195 ppm at the 2022–2024 90th percentile.

Montgomery County MUD No. 36

TX1700139

2025: chlorine 2.02 mg/L average; HAA5 12 ppb and TTHM 38 ppb highest LRAA. Lead 1.16 ppb and copper 0.138 ppm at the 2021–2023 90th percentile.

Montgomery County MUD No. 39

TX1700332

2025: chlorine 1.88 mg/L average; HAA5 12 ppb and TTHM 43 ppb highest LRAA. Lead 0.634 ppb and copper 0.108 ppm at the 2023–2025 90th percentile.

Montgomery County MUD No. 46

TX1700348

2025: chlorine 1.91 mg/L average; HAA5 17 ppb and TTHM 49 ppb highest LRAA. Lead 2.46 ppb and copper 0.258 ppm at the 2021–2023 90th percentile.

Montgomery County MUD No. 47

TX1700458

2025: chlorine 1.91 mg/L average; HAA5 14 ppb and TTHM 39 ppb highest LRAA. Lead 0.703 ppb and copper 0.146 ppm at the 2023–2025 90th percentile.

Montgomery County MUD No. 60

TX1700470

2025: chlorine 1.73 mg/L average; HAA5 16 ppb and TTHM 53 ppb highest LRAA. Lead 3.16 ppb and copper 0.135 ppm at the 2021–2023 90th percentile.

Montgomery County MUD No. 67

TX1700554

2025: chlorine 1.83 mg/L average; HAA5 19 ppb and TTHM 70 ppb highest LRAA. Lead was 0.833 ppb at the 2022–2024 90th percentile, with one sampled site reported over the action level; copper was 0.128 ppm.

Harris-Montgomery Counties MUD No. 386 - Creekside

TX1013305

2025: chlorine 1.46 mg/L highest average (the source reports ppm), HAA5 not detected, and TTHM 5.3 ppb highest detected. Lead was 1.4 ppb and copper 0.0354 ppm at the 2023 90th percentile. The report says this district obtains all water from Harris County MUD No. 387.

Measured facts

Published measurements

Free chlorine residual1.46–2.05 mg/L

PWS-specific 2025 average or highest-average values; see the applicable district record below.

Lead, 90th percentile0.634–3.32 ppb

Monitoring periods vary by PWS. MUD 67 separately reported one sampled site over the action level.

HAA5ND–21 ppb

Highest 2025 LRAA for the ten Woodlands Water MUDs; MUD 386 reports highest detected rather than LRAA.

TTHM5.3–70 ppb

Highest 2025 LRAA for the ten Woodlands Water MUDs; MUD 386 reports highest detected rather than LRAA.

LADS interpretation

What the evidence means—and does not mean

  • The summary ranges are navigation aids, not a Woodlands average. Each exact value remains attached to its district PWS, statistic, and monitoring period.
  • MUD 7 reported a monitoring-and-reporting violation, not a contaminant-limit exceedance: one of 30 samples was outside the approved site list, so the CCR says the system could not be sure of water quality during that monitoring window.
  • The MUD 67 report lists a 0.833 ppb lead 90th percentile and one sampled site over the 15 ppb action level. Those are different facts and both are preserved.
  • MUD 386 uses highest-detected statistics for disinfection byproducts and reports wholesale supply from Harris County MUD No. 387; its values are not collapsed into Woodlands Water LRAAs.
  • Address-level utility matching remains separate from market-level publication readiness. Confirm the district before applying any result to a property.
Measured fact

Values above stay tied to their named system, units, sample or report year, and official source.

Publisher interpretation

Planning language is educational context. It is not an official safety determination, diagnosis, ranking, or equipment prescription.

Primary evidence

Official sources

Evidence before equipment

Use the report as context—not as a substitute for the property.

Review water testing